Navigation
Home
:
Products
:
Gas Cabinets
Home
Company Information
Products
Gas Cabinets
Gas Panels
Valve Manifold Box
Siemens PLC Controller
Product Brochures
Contact Us
Site Map
Semi-Gas® Systems
Gas Distribution Products
Gas Distribution Systems:
Centurion
TM
Gas Cabinet
Valve Manifold Boxes
PLC Controller
UHP Manufacturing:
OEM Gas Panels
Support of Installed Equipment
Centurion
TM
Gas Cabinet Enclosure Design
Gas Cabinet Enclosure Design Features
Window
- Large self-closing, 1/4" wire-reinforced safety glass window allows exterior lighting inside cabinet and provides quick access to manifold components.
Face Shield
- Extremely tough polycarbonate sheet improves viewing angle while protecting the operator's face and eyes from injury.
User Interface
- Provides centralized and convenient access to critical cabinet information.
Door Louvres
- Provides air intake at door bottom.
Door
- Self-closing, self-latching beveled door with gasket provides tight seal to eliminate leaks.
Fire Sprinkler head
- UL approved beeswax coated with 155
o
F actuation temperature
Cyl-Safe
TM
cylinder mounting bracket
- Heavy steel bracket holds gas cylinders 6" to 11" in diameter. Equipped with polypropylene strap and chrome steel safety chain
Cylinder booster shelf
- Adjustable shelf for gas cylinders up to 34" tall. Raises cylinder to properly align with pigtail cylinder connection. Mounts directly to back wall of enclosure.
Cylinder scale ramp
- Allows easy installation and removal of cylinder.
Floor material
- Durable, corrosion-proof, non-skid material prevents damage to gas cabinet enclosure floor. Also helps secure gas cylinder scale for easy cylinder removal and replacement.
Adjustable Damper with Filter
Improved door & window seals
Diffused air inlets
Optimized gas cabinet design
Result...
A Gas Cabinet with Maximum air flow efficiency.
Cylinder Enclosure Specifications
(With Window Open)
(With Window Closed)
Cabinet Model
Exhaust Duct Diameter Size
Duct Flow (scfm)
Duct Velocity (fpm)
Window Opening (sq. inches)
Max Flow (scfm)
Max Velocity (fpm>
Dimensions in in. (cm)
W x D x H
1CE
6"
350
1780
72
150
50
15x23x87
38x58x221
2CE
6"
350
1780
187
200
75
25x23x87
64x58x221
3CE
8"
550
1575
259
320
100
40x23x87
102x58x221
1CE-200
8"
850
2435
72
500
425
15x23x87
38x58x221
Maximum flow is with fully-open damper on door. Minimum flow is with closed damper
Exhaust sizing should be based on maximum flow.
Minimum static pressure requirement at enclosure exhaust connection is -0.4 in. H
2
O except for 1CE-200 which is at -1.00 in H
2
O.
Damper on 1CE-200 must be adjusted to meet the 200 fpm ventilation velocity as required by the Uniform Fire Code. Height dimension includes controller